Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the the-events-calendar domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the broken-link-checker domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the woocommerce-eu-vat-number domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114
Rodent caused short circuiting of 440v bus bar - DEV imca
Skip to content

Rodent caused short circuiting of 440v bus bar

What happened?

A fire alarm was traced to the emergency generator room. A rodent had found its way into an emergency switchboard cabinet, causing a 440V short circuit, sparks and a foul smell. The board was isolated and the dead rat was removed.

What went wrong? What were the causes?

This appears to be an isolated incident wherein the rodent had come on board during port stay, and gained access to the emergency generator room when the door was opened during routine weekly testing. The vessel crew had not experienced the presence of rodents in recent months. There was no evidence (rat droppings) found anywhere on deck, in the accommodation or in the provision stores. All the doors to accommodation and hatches were kept closed at all times. Rat traps were in place at various locations.

What actions were taken? What lessons were learned?

  • The vessel was thoroughly searched for rodents in accommodation, the stores and on the deck after the incident; nothing was found;
  • Rat traps remained in place on deck and in accommodation and stores, and the baits renewed;
  • During port stay, rat guards were to be used on moorings;
  • During the loading of provisions/cargo, crew were to be extra vigilant for presence of rodents.

This incident appears to be unique in the IMCA safety flash database and for that reason is passed onto members.


IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.

IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.

IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.