Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the the-events-calendar domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the broken-link-checker domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the woocommerce-eu-vat-number domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114
Near-miss: 220v cable not isolated during work - DEV imca
Skip to content

Near-miss: 220v cable not isolated during work

A member has reported an incident in which a 220 volt mains cable was left live and exposed in situ during repair works. During the ‘routine’ maintenance task of outfitting a control room it was necessary to remove a light fitting to allow the removal of some fire retardant panels. The light was presumed to be isolated by a member of the work party, who tested this by use of a digital multi-meter and also by placing the tube back into the fitting to verify that it did not operate. The work party member then disconnected the fitting and left the exposed wires in situ.

When an instrument technician passed through the area on another task, he queried the status of the exposed wires. A further check was made on the wires and these were found to be live with 220v. The electrician was contacted and requested to isolate the circuit.

An investigating was conducting and the following conclusions were drawn:

  • On identifying that the light fitting required to be removed as part of the outfitting, the work party member took it upon himself to do this task, without checking;
    • the isolation status of the circuit with the supervisor
    • if an isolation confirmation certificate was in place
    • if a valid permit to work was in place for the task;
  • No consultation was made with the vessel electrician, who would be deemed responsible for the lighting circuits;
  • The work party member attempted to check the voltage of the circuit with a digital multi-meter, but did not operate this correctly and hence obtained a false reading, which led him to disconnect the fitting on a live circuit;
  • An immediate cause of this incident was that a digital multi-meter was used incorrectly to verify that the wires were not live (‘proving dead’). As there is the potential to have the digital multi-meter on the incorrect setting, it should never be used for proving dead. On this occasion, it is considered that the hold button had been inadvertently pressed on the unit which prevented a voltage from showing when proving dead.

Our member has also noted that there have been a number of other potentially fatal electrical incidents within its fleet since this incident:

  • A hard-wired, temporary 220v three phase cable was found hanging on a nitrogen quad, which had been disconnected at one end with the breaker only tripped, not isolated;
  • A near electrocution occurred due to the failure to apply a robust isolation.

In light of these recent near miss electrical incidents, the following preventative actions were taken:

  • Ensure all vessel departments were aware that any isolations carried out are done so in consultation with the appropriate electrical authority, and carried out by an approved isolator;
  • Ensure all vessel departments comply fully with company procedures for applying and controlling isolations -personal isolations or trips are not to be considered an acceptable means of isolating;
  • All ‘proving dead’ should be done with an approved unit which is designed for this purpose only. A recommended example of this would be the Martindale VI137002 voltage indicator and the PD440 proving unit;
  • Isolators should be familiar with the correct process of proving circuits are dead, including testing the device immediately before and after proving dead to ensure that the device is working correctly.

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.

IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.

IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.