Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the the-events-calendar domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the broken-link-checker domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the woocommerce-eu-vat-number domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114
Generator fire incident - DEV imca
Skip to content

Generator fire incident

A member has reported an incident in which there was a small fire onboard an offshore vessel. Excessive smoke and bright light were observed coming from a rental generator and the fire alarm was raised. The vessel fire team were called and they were able to suppress the fire within twenty minutes.

Generator cable caught fire - suspected worn wiring over time and lay out cables over the terminal
Generator cable caught fire – suspected worn wiring over time and lay out cables over the terminal
Phase 2 of the generator bus bar possibly contacting the generator casing, thus burning through phase 2 bus bar
Phase 2 of the generator bus bar possibly contacting the generator casing, thus burning through phase 2 bus bar

Our member identified the following immediate causes:

  • On board the vessel, two of three generators have a protection plate above the output plate, above the HV output terminals. This generator did not have that protection plate. There was evidence that the cable retaining bar was rusted and showing no signs of ever supporting cables. This would have meant that the starter motor cable was lying on top of the HV output terminals; over time this cable may have worn through due to vibration and causing a short circuit on phase 2, thus starting the fire;
  • On examination, the phase 2 bus bar appeared to be touching the generator casing (see Figure 2). As the bus bar burnt, the heat inside the generator caused the cables on the cable retaining bar to fall. However, the expectation was that the cable retaining bar would be blackened and not rusted.

Our member noted that root cause investigation was on-going, and the following lessons were learnt:

  • Proper maintenance and ‘routine’ check on generators and make sure no wiring laying across the terminal;
  • All generators should have appropriate protection cover to prevent water getting inside the terminal;
  • Fire extinguishers stood by near generators;
  • Internal nuts and bolts to be checked, fitted with lock washers as appropriate, and tightened properly.

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.

IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.

IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.