Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the the-events-calendar domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the broken-link-checker domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the woocommerce-eu-vat-number domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114
Faulty governors - DEV imca
Skip to content

Faulty governors

A member has reported a series of incidents involving the shutdown of two different diesel generators onboard a long term chartered vessel. On three separate occasions these incidents caused a full blackout, a partial blackout and the loss of a generator. The DP class II multi-purpose support vessel has four governors of the Woodward PG-EG58 type. During the incident investigation and fault finding process, two suspect governors were removed and replaced with two new units from a separate batch. The two suspect governors were returned to the manufacturer for inspection. The results of this inspection are summarised below:

  • Broken check valves were found in the governor oil pumps of both units;
  • The oil spray nozzle filters were blocked in both units. Small metal particles and pieces of check valve were identified;
  • The filter in the oil line to the torque motor was blocked in both units. Small metal particles and pieces of check valve were identified;
  • Foreign metal particles were found inside one of the governor units. These particles had caused the filters to become blocked, preventing oil flow to the hydraulic valve.

Although the governor can operate without the check valve, the pieces of broken valve were carried in the hydraulic system. This caused malfunction of the hydraulic valve.

Blocked oil spray nozzle
Blocked oil spray nozzle
Broken check valve
Broken check valve
 Foreign metal
Foreign metal

Safety Event

Published: 26 August 2008
Download: IMCA SF 13/08

IMCA Safety Flashes
Submit a Report

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.

IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.

IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.