Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the the-events-calendar domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the broken-link-checker domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114

Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the woocommerce-eu-vat-number domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/storm/sites/dev-imca-int-com-1/public/wp-includes/functions.php on line 6114
High potential near miss: Nitrogen hose failure during transfer of gas - DEV imca
Skip to content

High potential near miss: Nitrogen hose failure during transfer of gas

What happened?

As nitrogen gas was being transferred from the pipelay tower accumulators to storage bottles located within the pipelay HPU room, the pipelay supervisor noticed a sudden drop in pressure.  He immediately went to the door of the HPU room to assess the situation.  He could hear the sound of a high pressure gas release within the room, and decided not to go in.  He ran to the nearest emergency stop button located on the main deck to stop the system.

What were the causes?

The hose had been in place since 2010 and there was substantial degradation along its full length.  The hose was not identified on a hose register and therefore not subject to any planned maintenance or inspection regime.

What went wrong?

It was later identified that a supply hose had detached from its ferrule and approximately 165,000 litres of pure nitrogen was released into the room. Consequently this reduced the oxygen levels in the room to approximately 17.4% (normal oxygen content in the atmosphere is 20.8%).

Actions

  • All pressurised hoses should be correctly secured and coupled using properly rated hose whip check restraints.
  • All hoses and fittings should be visually inspected prior to use and should be examined regularly in service for wear and should be changed out as necessary or as part of a planned maintained schedule

Our member also:

    • Ensured adequate ‘Restricted Access’ signage is posted at all entrances to the nitrogen storage area;
    • Ensured suitable low oxygen detection alarms are installed within the immediate area.

Members may wish to refer to

Safety Event

Published: 25 August 2020
Download: IMCA SF 25/20

Relevant life-saving rules:
IMCA Safety Flashes
Submit a Report

IMCA Safety Flashes summarise key safety matters and incidents, allowing lessons to be more easily learnt for the benefit of all. The effectiveness of the IMCA Safety Flash system depends on Members sharing information and so avoiding repeat incidents. Please consider adding safetyreports@imca-int.com to your internal distribution list for safety alerts or manually submitting information on incidents you consider may be relevant. All information is anonymised or sanitised, as appropriate.

IMCA’s store terms and conditions (https://www.imca-int.com/legal-notices/terms/) apply to all downloads from IMCA’s website, including this document.

IMCA makes every effort to ensure the accuracy and reliability of the data contained in the documents it publishes, but IMCA shall not be liable for any guidance and/or recommendation and/or statement herein contained. The information contained in this document does not fulfil or replace any individual’s or Member's legal, regulatory or other duties or obligations in respect of their operations. Individuals and Members remain solely responsible for the safe, lawful and proper conduct of their operations.